Technical data • Entire device
Chap
ter 2
Te
chn
ica
l da
ta
55
Automation PC 820 User's Manual V 1.00
POWERLINK node switch
Double flash (approx. 1 Hz)
PRE_OPERATIONAL_2
The interface status is PRE_OPERATIONAL_2.
Managing Node (MN)
The MN begins with the cyclic communication (cyclic input data is not yet evaluated). The CNs are
configured in this status.
Controlled Node (CN)
In this status, the interface is normally configured by the manager. After this, a command changes the
status to PRE_OPERATIONAL_3 (triple flash).
Triple flash (approx. 1 Hz)
READY_TO_OPERATE
The interface status is READY_TO_OPERATE.
Managing Node (MN)
Normal cyclic and asynchronous communication. Received PDO data is ignored.
Controlled Node (CN)
The configuration of the interface is complete. Normal cyclic and asynchronous communication.
The PDO data sent corresponds to the PDO mapping used. However, cyclic data is not yet evaluated.
On
OPERATIONAL
The interface status is OPERATIONAL.
Blinking (approx. 2.5 Hz)
STOPPED
The interface status is STOPPED.
Managing Node (MN)
This status is not possible for the MN.
Controlled Node (CN)
No output data is produced and no input data is received. Only the appropriate command from the
manager can enter or leave this state.
POWERLINK node switch (x1, x16)
Both of these hex switches (x16, x1) are used to configure the
station number for the POWERLINK. Station numbers are
permitted between #00 and #FD.
The node switch is located behind the front cover. The front cover
must first be slid down to change the node switch.
Switch position
x1
x16
Description
0
0
Operation as managing node
0 ... D
1 ... F
station number
Operation as controlled node
E
F
Reserved
F
F
Reserved
Table 37: POWERLINK node switch (x1, x16)
Green - status
Description
Table 36: Status/Error LED as status LED - POWERLINK operating mode
x1
X16
EPL
Summary of Contents for Automation PC 820
Page 2: ...2 Automation PC 820 User s Manual V 1 00...
Page 4: ...4 Automation PC 820 User s Manual V 1 00...
Page 6: ...6 Automation PC 820 User s Manual V 1 00...
Page 212: ...212 Commissioning USB flash drive Automation PC 820 User s Manual V 1 00...
Page 246: ...Model number index 246 Automation PC 820 User s Manual V 1 00...