BPC Vent-Axia Integra Installation And Wiring Instructions Download Page 1

 
 
 
 
 
 
 
 
 
 

 
 

 
 
 

Heat Recovery Ventilation unit 

Installation and Wiring Instructions 

Stock Ref. N° 

456864

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. 
PLEASE SAVE THESE INSTRUCTIONS. 

Integra

 

220-240V~50Hz

Summary of Contents for Vent-Axia Integra

Page 1: ...Heat Recovery Ventilation unit Installation and Wiring Instructions Stock Ref N 456864 PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Integra 220 240V 50Hz ...

Page 2: ...e appliance by a person responsible for their safety 8 Young children should be supervised to ensure that they do not play with the appliance INSTALLATION GUIDANCE 1 The installer is responsible for the installation and electrical connection of the sentinel system on site It is the responsibility of the installer to ensure that the equipment is safely and securely installed and left only when mech...

Page 3: ...heat exchanger for maintenance and servicing purposes 3 If appropriate provide mains electrical supply and drainage system in the vicinity of the installation site 4 Typically there are three forms of installation for the Integra To mount the unit on joists Place the unit across two beams and attach the appropriate cabling drainage and ductwork to the unit with the Vent Axia logo facing up For opt...

Page 4: ...TERS JOIST CONDENSATION DRAIN THE UNIT SHOULD SLOPE DOWNWARDS BY 2 TOWARDS THE CONDENSATE DRAIN INTEGRA 50 x 25 BATTEN MAINS TERMINAL BOX RAFTERS CONDENSATION DRAIN THE UNIT SHOULD SLOPE DOWNWARDS BY 2 TOWARDS THE CONDENSATE DRAIN INTEGRA MAINS TERMINAL BOX STRAP HANGERS ...

Page 5: ...tale exhaust air to outside Fig 2a Integra operated by a Trickle Boost switch SUSPENDED CEILING STRAP HANGERS MAINS TERMINAL BOX INTEGRA CONDENSATION DRAIN THE UNIT SHOULD SLOPE DOWNWARDS BY 2 TOWARDS THE CONDENSATE DRAIN N2 L N1 3A N L TRICKLE BOOST TRICKLE BOOST SWITCH FAN UNIT TERMINAL BLOCK 50Hz 220 240V 455213 Not supplied ...

Page 6: ...t Response humidity sensor Fig 2c Integra Controlled by a single Trickle Boost switch via a 150VA transformer N2 L N1 3A N L TRICKLE BOOST AMBIENT RESPONSE HUMIDITY SENSOR FAN UNIT TERMINAL BLOCK 5 4 3 L N 563501 220 240V 50Hz Not supplied ...

Page 7: ...7 Fig 2d Integra controlled via two sensors switches and a 150VA transformer to give 3 running speeds ...

Page 8: ...r needs to be connected to the switch as shown The L N1 N2 and E terminals should be connected as per the relevant Fig 2 After installation ensure that with the switch set to extract only that there is no supply airflow Note If the summer bypass is used without the 150VA transformer the unit will run at boost in trickle and boost setting ...

Page 9: ...to the unit 2 Remove the cover from the unit after releasing the four retaining screws 3 Unscrew and remove the single screw retaining the heat recovery cell 4 Withdraw the heat recovery cell 5 Wash the heat recovery cell in warm water using a mild detergent then ensure that it is thoroughly dried NOTE Keep water away from all electrical components and wiring inside and outside the unit There may ...

Page 10: ...emand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Internal 5 External Mixing Rate of Non Ducted BVUs not intended to be equipped with one duct connection on either supply or extract air side N A Position and description of visual filter warning for RVUs intended for use with filters including ...

Page 11: ...Notes ...