9E-864C
StepMetrix™ Installation Instructions
4
1.
StepMetrix location in an adjoining building or passageway (ideal location)
l864_1
If routed together, the AC wires will couple
transients onto the DC wires (that is, the DC wires
will pick up electrical noise). Communication and
DC cables can be run in t he same conduit. Such
noise could lead to poor or intermittent operation
of any cont roller served by the powe r supply.
Though no distance restrictions apply to conduits
for AC and DC wi res perpendicular to o ne
another, parallel conduit for AC and DC wi res
must be a mi nimum of 12 inches (305 mm) from
each other to prevent transients from coupling.
•
Memory: 512 MB RAM
•
Hard Drive: 10 GB Hard Drive
•
Data Storage: 100 MB
•
Network: Ethernet connector (Optional second
Ethernet connector for additional network)
•
Backup Device: Secondary Hard Drive for full
backup
•
DVD – R for data and program storage
•
CDROM – R for program only
1.2.7
Network Controller
If the dairy fa rm is equipped with a Pro Vantage 2050
Network Controller, the dairy operator must have
Version 2.1.41 or higher of EZ cow software
•
This product requires uninterrupted AC power to
operate properly. To ensure that it will not operate
intermittently, we recommend that a qualified (or
licensed, if applicable) electrician evaluate the
load on the farm and barn electrical service
entrance before you install and use the
product/system to ensure that it
will have
adequate power.
1.2.8
SMX ISO ID Site Evaluation
•
A site evaluation must be p erformed for
StepMetrix installations using ISO ID antennas.
Any needed corrective actions must be take n
before the installation of the StepMetrix.
•
Before connecting power to the sy stem parts, a
lightning arrestor must be installed on AC power
lines, main pole, and p ower panels serving
BouMatic automation equipment. Refer to th e
Lightning Arrestor instructions, 9P-476.
•
Refer to site evaluation instructions 9E-892 when
performing
the
evaluation.
1.2.6
Dairy PC
•
Operating System: Windows 2000
•
Processor: Intel Pentium III or AMD Athlon
•
Monitor: SVGA Monitor, capable of resolution
1024x768 and 16-bit color depth
•
Pointing Device: Mouse or equivalent