WASP™ NEST4 Smart Receiver and Gateway Operations Manual
- 23 -
3.2.7.8 Setting Temperature Multiplier Factor
To change the default setting highlight the parameter
and modify the PERCENT factor using the
UP/DOWN and LEFT/RIGHT arrows. Tap
OK
to
save.
3.2.7.10 Temperature Calibration
To set from the settings screen, scroll to, and select
TEMP CALIBRATION
to calibrate the sensor
temperature reading to a reference reading. Using
the UP/DOWN and LEFT/RIGHT arrows enter the
reference reading from an external device such as
thermometer gun. Tap on
OK
to save the calibration
or tap on
CANCEL
to return to the settings screen.
Example: If the WASP™ reads 23 °C and the
thermometer gun you are reading reads 26 °C, set
the REF point to 26 °C for that sensor. This automatically applies a preset multiplier to the sensor
ensuring accuracy.
TEMP CALIBRATE (REF,'C)
21'C CRI=4 WRN=1 13:46 NOV 24/10
CANCEL
BACK
OK
REF C
025.2