Initial commissioning
5–4
1070 066 091-102 (01.08) GB
5.2
Enhanced programming
5.2.1
Initializing absolute encoders
.
This function can only be performed for motors equipped with multi-
turn encors (rating plate information on encoder: EQN 1325).
L
Load P-0-0006 (Position encoder type – motor encoder) into the monitor and
set the value to 1 (= absolute encoder function active).
In this case, the software supports you with the determination of the absolute
dimension offset (S-0-0177).
L
Turn the power supply of the drive on. Enable the drive with a zero setpoint.
The drive is stopped, the torque is active.
L
Move the axis to the mechanical zero position.
L
Select
EXTRAS
"
DRIVE FUNCTIONS
"
INIT ABSOLUTE ENCODER.
L
Click on ”Start”
L
Click on ”No” to abort the function.
Clicking on ”Yes” will start the measurement.
After the measurement, the system will display the current offset:
L
Close the dialog.
L
Execute the ”Save main memory” command (cf. section 4.6.2).
L
Reboot the drive.