12.9.9 Sleep / Wake Function
This function is used to achieve the maximum extent of energy-saving according
to type of loads in actual applications.
Code
Name
Setting range
Default
Min.
Attri.
E5.15 Sleep level
0.00...[E0.09] Hz
0.00
0.01
Run
E5.16 Sleep delay
0.0...3,600.0 s
60.0
0.1
Run
E5.17 Sleep boost time
0.0...3,600.0 s
0.0
0.1
Run
E5.18 Sleep boost amplitude
0.0...100.0 %
0.0
0.1
Run
E5.19 Wake up level
0.0...100.0 %
0.0
0.1
Run
E5.20 Wake up delay
0.2...60.0 s
0.5
0.1
Run
The frequency converter may go into the sleep mode when all the conditions be-
low are met:
●
[PID feedback] > [E5.19] 'Wake up level'
●
[PID output] < [E5.15] 'Sleep level'
●
[Duration] t ≥ [E5.16] 'Sleep delay'
Bosch Rexroth AG
Functions and Parameters
VFC 3210
146/253