12.9.8 PID Status Indication
Code
Name
Setting range
Default
Min.
Attri.
E4.32 PID engineering value detection width
0.01...100.00
1.00
0.01
Run
E2.15 Relay 1 output selection
18: PID reference engi-
neering value arrival
1
–
Stop
[E4.32] 'PID engineering value detection width' is used to set the tolerance win-
dow between [d0.70] 'PID reference engineering value' and [d0.71] 'PID feed-
back engineering value'. When the difference between reference and feedback is
within the detection width, the value arrival signal will be active via DO1 output.
Set [E4.32] =
│
[d0.70] - [d0.71]
│
/[d0.70] x 100 %
Fig. 12-40: PID engineering value detection width
VFC 3210
Bosch Rexroth AG
Functions and Parameters
DOK-RCON04-VFC3210****-IT01-EN-P
145/253