12.5.2 Run Command Source
First and second run command source configuration
Code
Name
Setting range
Default
Min.
Attri.
E0.01 First run command source
0...2
0
–
Stop
E0.03 Second run command source
0...2
1
–
Stop
●
0: Operating panel.
Control the frequency converter for run and stop with <Run>, <Stop> buttons
on the operating panel.
Control the running direction by setting parameters U0.00 'Direction control
by panel' and E0.17 'Direction control'.
●
1: Multi-function digital input. Control the frequency converter for run, stop
and running direction by setting digital inputs.
●
2: Communication. Control the frequency converter for run, stop and running
direction with Modbus communication protocol.
Switch between first and second run command source
Code
Name
Setting range
Default
Min.
Attri.
E1.00 X1 input
31: Second run command source activation
35
–
Stop
E1.01 X2 input
36
–
Stop
E1.02 X3 input
0
–
Stop
E1.03 X4 input
0
–
Stop
If status of the selected terminal is changed when converter is running, the run
command source will be switched and the converter will freewheel to stop. The
active / inactive of digital input is triggered by voltage level.
Stop command via panel <Stop> button
After the run command source configuration, set U0.01 'Stop button control' to
define the function of <Stop> button on the operating panel.
Code
Name
Setting range
Default
Min.
Attri.
U0.01 Stop button control
0: Active only for operating panel control
1: Active for all control methods
1
–
Run
Bosch Rexroth AG
Functions and Parameters
VFC 3210
108/253
DOK-RCON04-VFC3210****-IT01-EN-P