12.4.2 Select the Frequency Setting Source
General setting
Different frequency setting sources can be selected by setting parameter E0.00
'First frequency setting source' or E0.02 'Second frequency setting source'.
Code
Name
Setting range
Default
Min.
Attri.
E0.00 First frequency setting source
0...21
0
–
Stop
E0.02 Second frequency setting source
0...21
2
–
Stop
●
0: Panel potentiometer
The setting frequency is set by adjusting the potentiometer on the operating
panel.
●
1: Panel button
The setting frequency is set by parameter E0.07 'Digital setting frequency'.
Pressing <▼> and <▲> buttons on the operating panel will decrease and in-
crease the output frequency respectively when the frequency converter is run-
ning.
●
2: AI1 analog input
The setting frequency is set by AI1 input.
●
11: Digital input Up / Down command
The setting frequency is set by command of Up / Down / Reset via digital in-
puts.
●
20: Communication
The setting frequency is set by engineering software, PLC or other external
device via Modbus protocol.
●
21: Multi-speed settings
The setting frequency is set by multi-speed settings.
Bosch Rexroth AG
Functions and Parameters
VFC 3210
90/253
DOK-RCON04-VFC3210****-IT01-EN-P