①
Right
②
Left
Fig.7-3:
Cable routing on the left and the right when using the RS-232-C interface
Cable routing Ethernet
The following figure shows the cable routing using the Ethernet interface.
①
Right
②
Left
Fig.7-4:
Cable routing on the left and the right when using the Ethernet interface
7.2
Emergency Stop Button and Gray Stop Button
The device is available with a red-yellow emergency stop button as well as with
chapter 1 "System Presentation" on page 5
.
The emergeny stop button or the stop button is dual circuit wired and the con‐
tacts are realized as NC contacts.
Devices with gray stop button
Optionally, the IndraControl VCH 08.1 device is also available with a grey stop
button instead with a red-yellow emergency stop button. In practical terms, the
gray stop button has the same functionality as the red-yellow emergency stop
button. By means of its coloring, the gray stop button is to prevent the operator
from using the emergency stop button when the hand-held terminal is discon‐
nected. The gray stop button complies with all of the mechanical aspects of EN
ISO 13850 and merely differs in color.
The IndraControl VAC 30.2 connection module is equipped with an automatic
stop circuit jumpering. This feature allows the operator the connection or dis‐
DOK-SUPPL*-VCH*08.1***-PR02-EN-P
Rexroth IndraControl VCH 08.1 Hand-held Terminal
Bosch Rexroth AG
69/117
Pin Assignments of the IndraControl VCH 08.1