15.2 FAULT TABLE
Table 19: Malfunction table for SYDFE1 control systems
Malfunction
Possible cause
Remedy
Error message present:
Indicator lamp “Err.“ on the
front panel of the VT 5041-3X
is ON
Enable not granted: Indicator lamp “En.“ is
out.
Apply 24 V to contact 26c
Supply voltage missing or fuse F1 defective:
Indicator lamp “Ub“ is out
Apply 24 V to contact 32a, connect 28a to
ground (0 V)
Cable break of the swivel angle sensor cable
Check wiring (see 7.6.5 “Connecting the
swivel angle sensor“, page 57)
Cable break of the valve position sensor cable Check wiring (see 7.6.4 “Connecting the
valve position transducer“, page 55)
Cable break of the proportional solenoid cable Check wiring (see 7.6.6 “Connecting the
solenoid of the proportional valve“, page
When monitoring of the control error is
activated (jumper J9 set/ON), excessive
control error (valve command value > +4 V or <
-4 V) for longer than 1 sec.
For further notes, see page 63.
Defect or short-circuit of auxiliary voltages on
the control electronics
Contact Rexroth Service
Humming noise in the pressure
control or fluctuations in
pressure/flow
Air cushion around the sensor
Bleed control system, pre-load valve (see
8.1.8 on page 67) and pipes completely
Problem with the cable shield
Connect shield to ground
Unfavorable place of installation/mounting
technique for the pressure transducer
Change place of installation (e.g.
suspended mounting, no minimess line,
no throttling point between pump and
pressure transducer)
Improperly high gain of the actual pressure
value
Reduce weighting of the actual pressure
value and pressure command value, see
page 68
Screaming noise
Oil level in the tank too low; pump partly
aspires air
Top up oil
Pump aspires air
Change routing of the suction line
Suction line leaky
Seal suction line
Pump cavitates when pressure is reduced
Diagnostics: Measure, whether overshoots
occur in the pressure line at individual
pressure levels, e.g. pressure almost 0 bar
and, at the same time, negative swivel angle
Optimize controller, reduce command value
via a ramp or in steps.
Fluid in the tank mixed with air; cooling and/or
filtration circuit leaky
Seal