Diagnostic Messages for Parameter Errors
DOK-CONTRL-ILPSDO8****-AW04-EN-P
Bosch Rexroth AG
Rexroth Inline Module with Safe Digital Outputs R-IB IL 24 PSDO 8-PAC
13.3
Diagnostic Messages for Parameter Errors
Error code
Error cause
Remedy
dec
hex
64
40
The parameterized F_Destination_Address does not
match the PROFIsafe address set on the safety module (F-
Module).
Make sure that the PROFIsafe address of the
safety module and the value in F_Destina-
tion_Address are the same.
65
41
Invalid parameterization of F_Destination_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct value.
66
42
Invalid parameterization of F_Source_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct value.
67
43
Invalid parameterization of F_WD_Time.
A monitoring time of 0 ms is not permitted.
Correct value.
68
44
Invalid parameterization of F_SIL.
The safety module (F-Module) cannot support the required
SIL.
Use a device with the required SIL.
The safety module achieves SIL 3, maximum.
69
45
Invalid parameterization of F_CRC_Length.
The CRC length generated by the safety module
(F-Module) does not match the required length.
Check device description.
70
46
Invalid F-Parameter record version.
The safety module (F-Module) version does not match the
required version.
Check device description.
Only V2 mode permitted.
71
47
The checksum determined by the safety module
(F-Module) via the PROFIsafe parameters (CRC1) does
not match the CRC1 transmitted in the parameter tele-
gram.
Check F-Parameters, repeat calculation.
255
FF
During active process data communication, a new
F-Parameter block was received, which differs from the F-
Parameter block currently used.
Only send modified parameter data when pro-
cess data communication is not active.
Incorrect type ID for the F-Parameter block (F_Block_ID).
Check device description.
Table 13-2
F-Parameter parameter errors
Error code
(hex)
Error cause
Remedy
03F2
iPar_CRC is incorrect
Check iParameters, repeat calculation.
03FA
iPar_CRC is not equal to F_iPar_CRC
Apply correct value.
03FB
PST_Device_ID is incorrect
Correct value (20
hex
for
R-IB IL 24 PSDO 8-PAC).
03FC
F_Destination_Address in the iParameters is incorrect
Correct value.
Make sure that the value set under F_Destina-
tion_Address and the value that you have set via
the 10-pos. DIP switch are the same.
03FD
Incorrect order of iParameter blocks
Check infrastructure components.
Table 13-3
iParameter parameter errors