Assembly
7.2.15
Main switch tripped (X8)
Connection:
to X8; STKK, grid 3.5 mm, 3-pole,
max. 1.5 mm
2
.
Mating connector is comprised in the delivery.
Cable length:
max. 10 m at 0.75 mm
2
max. 75 m at 1.5 mm
2
Cable type:
unshielded, VDE 0281, 0812 (e.g.: Ölflex)
When the timer detects a current flow in the primary circuit which is not
in connection with a welding schedule („Weld without command“ func
tion), the main switch is tripped:
•
The timer signals „Main switch tripped“ or „Weld without command“
and
•
short-circuits the terminals 2 and 3 at X8 (changeover switch; floa
ting).
If main switches with an appropriate functionality are used, this will
automatically trip the circuit breaker (main switch), and thus the power
supply, provided that X8 has been wired accordingly (ncc/noc).
X8
1
2
3
Device for trip
ping the main
switch
No error state:
Terminals 1 and 2 are shorted
Timer detects error state:
Terminals 2 and 3 are shorted
Load:
24 V
DC
, max. 6 A
42 V
AC
, max. 1 A
Timer
Fig.46:
Connection terminals for main switch trip
ENGLISH
Summary of Contents for Rexroth PST 6 0 Series
Page 12: ......
Page 152: ...1070080029 05 Bosch Rexroth AG Electric Drives and Controls PST 6xx0 152 330 Notizen Notes ...
Page 170: ...1070080029 05 Bosch Rexroth AG Electric Drives and Controls PST 6xx0 170 330 Notes ENGLISH ...
Page 176: ......
Page 316: ...1070080029 05 Bosch Rexroth AG Electric Drives and Controls PST 6xx0 316 330 Notes DEUTSCH ...
Page 320: ...1070080029 05 Bosch Rexroth AG Electric Drives and Controls PST 6xx0 320 330 Notes DEUTSCH ...