That results in the greatest absolute value of 30.2 V as upper voltage limit. The
lowest absolute value of 18.5 V is the lower voltage limit.
24 V DC cabling
PE bar
B
Overvoltage category I
XS1
FE
VEP
24 V
6 mm² (blue)
A
A
0 V
2
1
2
2
1
10 mm (green/yellow)
2
①
Easy to remove and visible
②
Cable length b24 V power sup-
ply unit and the VEP is 6 m max. at a
minimum cross-section of 0.75 mm
2
. Ca-
ble length b24 V power supply
unit and the VEP is 10 m max. at a mini-
mum cross-section of 1.5 mm
2
. An addi-
tional power supply unit is required if
the length exceeds 10 m.
A
Insulated terminal block
B
Non-insulated terminal block
FE Functional earth
Fig. 10-8: Wiring the Embedded Terminal
11 Commissioning
The product can be used directly. No configuration is required.
To commission the device, proceed as follows:
During the first commissioning, the configuration applications "Touch calibra-
tion" and the "Rexroth settings" start automatically. They are described in the
project planning manual "Rexroth IndraControl V Devices Operating Systems" (see
tab. 1-1 "Related documents" on page 2
). For newly delivered devices, these set-
tings are already done ex works.