Rexroth IndraDrive
Command Diagnostic Messages
9-73
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0606 Reference mark not detected
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command for drive-controlled homing (C0600)
an error was detected.
Cause:
If a
•
distance-coded measuring system or
•
an incremental measuring system
are homed, the maximum travel distance during the homing procedure is
known. If there isn
’
t any reference mark detected within this distance, the
C0606 Reference mark not detected
error message is generated and
the homing procedure is aborted with error.
Note:
In the case of linear non-distance-coded measuring systems,
the travel distance is unknown if "0" was entered in parameter
P-0-0153, Optimum distance home switch-reference mark
.
This normally is the case if the linear scale does not have any
reference marks in equal, known distances. In this case
monitoring for faulty reference mark detection cannot be
carried out.
Remedy:
•
check the measuring system to be homed and its cabling
•
check the parameterization
•
in the case of incremental measuring systems, check the reference
mark detection by executing the
P-0-0014, C1400 Command Get
marker position
command