Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0604 Homing of absolute encoder not possible
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command for drive-controlled homing (C0600)
an error was detected.
Cause:
By the encoder selection in
S-0-0147, Homing parameter
an absolute
measuring system was selected. The command for drive-controlled
homing can only be executed if the
P-0-0012, C0300 Command Set
absolute measuring
command had been activated before.
Remedy:
First activate the
P-0-0012, C0300 Command Set absolute measuring
command and then start the
S-0-0148, C0600 Drive-controlled homing
procedure command
. Doing this the absolute reference point is
established.