C0245 Operating mode configuration (->S-0-0022) not allowed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
S-0-0128, C0200 Communication
phase 4 transition check
an invalid operating mode configuration was
detected.
In the operating mode parameters it is not allowed to parameterize
synchronization modes with outer position control loop (phase
synchronization or electronic cam shaft) with different control encoders.
•
S-0-0032, Primary mode of operation
•
S-0-0033, Secondary operating mode 1
•
S-0-0034, Secondary operating mode 2
•
S-0-0035, Secondary operating mode 3
•
etc.
Cause
Remedy
Operating mode configuration is invalid (phase
synchronization or electronic cam shaft with different
control encoders)
Parameter contents of operating mode parameters have
to be changed is such a way that invalid operating mode
configuration no longer occurs (the respective operating
mode parameters are listed in
S-0-0022, IDN list of
invalid operating data for communication phase 3
)
For removing command errors see "Command Errors"
C0245 - Attributes
Display:
C0245
Mess. no.:
C0245 (hex)
Operating Mode Parameters