9-22
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0109 Position of data record in MDT (S-0-0009) even
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
S-0-0127, C0100 Communication
phase 3 transition check
an error was detected.
Cause
Remedy
Parameter
S-0-0009, Position of data record in
MDT
contains an even value. This is not allowed.
Parameter
S-0-0009, Position of data record in MDT
must be parameterized with an odd value
Note:
The definition of the S-0-0009 parameter is the responsibility
of the control unit manufacturer and is specified by SERCOS.
For removing command errors see "Command Errors"
C0109 - Attributes
Display:
C0109
Mess. no.:
C0109 (hex)
C0110 Length of MDT (S-0-0010) odd
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command
S-0-0127, C0100 Communication
phase 3 transition check
an error was detected.
Cause
Remedy
Parameter
S-0-0010, Length of master data
telegram
contains an odd value. This is not allowed.
Parameter
S-0-0010, Length of master data telegram
has to be parameterized with an even value
Note:
The definition of the S-0-0010 parameter is the responsibility
of the control unit manufacturer and is specified by SERCOS.
For removing command errors see "Command Errors"
C0110 - Attributes
Display:
C0110
Mess. no.:
C0110 (hex)