Warning Diagnostic Messages (Exxxx)
8-23
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E2048 Interpolation acceleration = 0
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
In operating states/ operating modes in which the drive-internal position
command value interpolator is active, the preset acceleration effective in
the drive is monitored with regard to the value "0" [without acceleration
(deceleration) a preset velocity can never be reached; slowing down with
a deceleration "0" isn
’
t possible either].
Note:
The input values of the parameters are converted to a drive-
internal format. This is why input values > "0" can, internally,
also cause an acceleration = "0". The parameter values which
drive-internally still cause an acceleration >
"0" can be
calculated.
See also Functional Description "Drive-Internal Display of
Position Data".
The monitor is active in the following operating modes or operating states:
•
drive-internal
interpolation
•
drive-controlled
positioning
•
positioning block mode
•
Drive
Halt
•
position
spindle
•
drive-controlled
homing
•
automatic control loop setting
•
...
Cause
Remedy
Incorrect acceleration is preset (value = "0")
(vgl.
S-0-0260, Positioning acceleration
,
S-0-0042,
Homing acceleration
,
S-0-0138, Bipolar
acceleration limit value
,
S-0-0359, Positioning
deceleration
)
Check parameterization or cyclic command value of
control unit and set value for preset acceleration > "0"