Rexroth IndraDrive
Warning Diagnostic Messages (Exxxx)
8-17
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E3105 Plausibility error of safety related operating mode
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When the safety technology has been activated, this warning only occurs
in normal operation. When a safety function is selected, the cause of the
error causes the error
F7042 Plausibility error safety related operating
mode
to be triggered.
Cause
Remedy
During comparison of active safety function of
channel 1 and channel 2 a difference was detected
for more than 5 seconds
Reboot drive. If drive generates warning again,
hardware has to be replaced
E3105 - Attributes
Display:
E3105
Mess. no.:
E3105 (hex)
E3106 System error channel 2
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When the safety technology has been activated, this warning only occurs
in normal operation. When a safety function is selected, the cause of the
error causes the error
F3146 System error channel 2
to be triggered.
Cause
Remedy
System error on channel 2
Reset module, replace hardware if error occurs
repeatedly
E3106 - Attributes
Display:
E3106
Mess. no.:
E3106 (hex)