F7030 Pos. window for safety rel. operational stop exceeded
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The drive is shut down with velocity command value reset.
The drive automatically switches to safety related standstill and the output
stage is switched off via two channels.
As soon as the axis has stopped the safety door can be opened.
Cause
Remedy
In safety function "safety related operational stop",
position window defined in
P-0-3230, Monitoring
window for safety related operational stop
has
been exceeded
Start command
S-0-0099, C0500 Reset class 1
diagnostics
in order to clear error and then set drive
enable again.
If necessary, change parameterization of
P-0-3230,
Monitoring window for safety related operational
stop
in useful way
F7030 - Attributes
Display:
F7030
Mess. no.:
F7030 (hex)