11-14
Commissioning
MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Note:
For initial start of kit motors it is important first to check correct
direction of movement in torque/force control!
For moving the drive during initial start a velocity-controlled
operating mode is useful!
Activate command value box of DriveTop
(via DriveTop menu bar
"Extras" – "Virtual battery box" – "Virtual battery box adjustments" set
travel profile of selected operating mode)
.
Note:
Reduce velocity and torque/force limits to safe values!
17. Now put drive into operation:
CAUTION
Possible damage caused by errors when
controlling motors and moving parts!
⇒
Only enable axis from safe initial position! E-Stop
pushbutton must be available in position easy to
reach!
Set drive enable
(activate "Enable" button with cursor)
!
Negatively acknowledge warning dialog for possibly dangerous
movements if requirements for safe drive functioning have not been
fulfilled
(activate "Cancel" button with cursor)
!
Positively acknowledge warning dialog if requirements for safe drive
functioning have been fulfilled
(activate "OK" button with cursor)
!
18. Correctly moving the drive according to command values preset by
DriveTop confirms operatability of drive.
If drive does not follow command values, shut it down fast as can
(activate "Drives OFF" button with cursor or press E-Stop
pushbutton)
.
If drive follows command values, this is the basis for further
commissioning steps regarding master communication via NC and
further machine-axis-related functions!
11.2 Commissioning Machine
Axes
Overview and Practical Tips
Brief Description
Before commissioning machine axis-specific functions it is useful to make
sure that the drive, consisting of controller, motor and motor encoder, is
operational. The best way to do this is the initial start of the drive with the
PC-based commissioning tool "DriveTop" by Bosch Rexroth (see "Initial
Start with the DriveTop Commissioning Tool").
The commissioning of machine axis-specific functions should also be
carried out via DriveTop, if possible. The advantage is that the correct
sequence of an axis-specific function can be configured and ensured
independent of the control unit. Further commissioning of the drive, with
widely complete configuration, is then easier for the control unit.