MPH-02, MPB-02, MPD-02
Handling, Diagnostic and Service Functions
10-21
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
The parameters P-0-0192 and P-0-0193 have a stack structure and
contain, in chronological order, the diagnostic message numbers or the
counts of the operating hours counter of the last
50 errors
that occurred.
Note:
The count of the operating hours counter at the time the last
error occurred is entered at the top of parameter P-0-0193 and
the diagnostic message number of the last error occurred at
the top of parameter P-0-0192.
If the error concerns the power section it is additionally stored in
parameter
P-0-0194, Error memory of power section
.
The last 13 errors that occurred and the respective count of the operating
hours counter (cf. P-0-0191) are stored in this parameter.
The error
F8060 Bridge fuse
, for example, is an error in the power
section. This error would be displayed both in parameter P-0-0193 and in
parameter P-0-0194.
10.3 Diagnostic System
Coded Diagnostic Drive Messages
Brief Description
The drive provides a diagnostic system including different possibilities that
are basically divided into two groups:
•
recognizing and displaying the current drive status by means of drive-
internal, priority-dependent generation of diagnostic messages
•
collective messages for diverse status messages
Additionally, there are parameters for all important operating data the
values of which can be transmitted both via master communication (e.g.
SERCOS) and a parameterization interface (RS-232/485 in the ASCII
protocol or SIS protocol; see section "Serial Communication").
Pertinent Parameters
•
S-0-0030, Manufacturer version
•
S-0-0095, Diagnostic message
•
S-0-0140, Controller type
•
S-0-0142, Application type
•
S-0-0375, List of diagnostic numbers
•
S-0-0390, Diagnostic message number
•
P-0-0009, Error number
•
P-0-0478, Logbook event
•
P-0-0479, Logbook time stamp
Drive-Internal Generation of Diagnostic Messages
Operating states, activities and reactions of the drive controller are
detected by drive-internal generation of diagnostic messages and appear
in coded form on the display of the control panel. In addition, these
diagnostic messages can be transmitted to the master (control unit or
commissioning software, e.g. DriveTop).
Error Memory in Power Section