5.6
KNK03 mains filter
5.6.1
KNK03 data sheet
Technical data - currents, voltages, power
Description
Symbol
Unit
KNK03.1A-NR-B0012-P-U226-A4-NNNN
Degree of protection according to
IEC 60529
IP
IP65
Listing in accordance with UL
standard
UL 61800-5-1
Listing in accordance with CSA
standard
CSA C22.2 No. 274-13
Mass
m
kg
20.00
Three-phase mains voltage at TN-
S, TN-C, TT mains
U
LN
V
AC 380…500
Mains voltage three-phase at Cor‐
ner-grounded-Delta mains
1)
U
LN
V
tbd
Three-phase mains voltage at IT
mains
2)
U
LN
V
tbd
Tolerance rated input voltage U
LN
%
±10
Continuous current
I
L_cont
Typical inductance per winding at
I
cont
L
typ
µH
2
Power dissipation at continuous
current and continuous DC bus
power respectively
3)
P
Diss_cont
W
160
Insulation resistance at 500 V DC
R
is
Mohm
tbd
Required wire size in accordance
with NFPA 79 and UL 508 A (in‐
ternal wiring);
4)
A
LN
AWG
tbd
Last modification: 2016-01-20
1) 2)
Mains voltage > U
LN
: Use a transformer with grounded neutral
point, do not use autotransformers!
3)
Plus dissipation of braking resistor and control section
4)
Copper wire; PVC-insulation (conductor temperature 90 °C;
T
a
≤ 40 °C) in accordance with NFPA 79 chapter 12 and
UL 508A chapter 28
Tab. 5-16:
KNK - Technical data - currents, voltages, power
DOK-INDRV*-KCU02+KSM02-PR03-EN-P
Bosch Rexroth AG
99/337
Rexroth IndraDrive Mi Drive Systems with KCU02 KSM02, KMS02/03, KMV03, KNK03
Technical data of the components