14.1.3
Digital inputs (safety technology S options)
The digital inputs correspond to IEC 61131, type 1.
Data
Unit
min.
max.
Allowed input voltage
V
-3
30
High
V
15
30
Low
V
-3
5
Current consumption
mA
2
5
Tab. 14-3:
Digital inputs (safety technology S options)
Time behavior
Description
Unit
min.
max.
Test pulse width (t
PL
)
µs
0
1000
Percentage of High time (T
PH
/T
P
×100%)
%
90
100
Phase shift between two test pulses on both channels
(φ)
ms
-
-
Tab. 14-4:
Time behavior
370/407