Rexroth IndraDrive
Mechanical Mounting
6-9
DOK-INDRV*-HMV-*******-PR01-EN-P
electronic
equip.
Eb0002f1.fh7
incorrect
cooling
unit
control cabinet
air inflow
air outflow
correct
control cabinet
air inflow
air
duct
electronic
equip.
cooling
unit
Fig. 6-10:
Arrangement of the cooling unit on the front of the control cabinet
Condensation occurs when the temperature of the unit is lower than the
ambient temperature.
•
Set cooling units with temperature adjustment to the maximum
surrounding temperature and no lower.
•
Set cooling units with traced temperature so that the interior
temperature of the control cabinet is no lower than the temperature of
the surrounding air. Set the temperature delimitation to the maximum
surrounding temperature.
•
Only use well-sealed control cabinets so that condensation cannot
arise as a result of warm and moist external air entering the cabinet.
•
In the event that control cabinets are operated with the doors open
(start-up, servicing etc.) it is essential to ensure that after the doors are
closed the drive controllers cannot at any time be cooler than the air in
the control cabinet, as otherwise condensation can occur. For this
reason ample circulation must be provided inside the control cabinet to
avoid pockets of heat.
Avoiding Condensation
Summary of Contents for Rexroth IndraDrive HMV01.1E-W0030
Page 30: ...5 2 Transport and Storage Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 40: ...6 10 Mechanical Mounting Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 88: ...9 8 Control Mains Contactor Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 122: ...13 22 Appendix Rexroth IndraDrive DOK INDRV HMV PR01 EN P Fig 13 25 HFD01 2 480 0026 ...
Page 123: ...Rexroth IndraDrive Appendix 13 23 DOK INDRV HMV PR01 EN P Fig 13 26 HFD02 2 480 0026 ...
Page 130: ...14 6 Index Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 131: ......