Transporting the Devices
Conditions
temperature
-25 ... 70 °C
relative humidity
5 ... 95%;
climatic category 2K3
absolute humidity
1 ... 60 g/m
3
climatic category 2K3
moisture condensation
not allowed
icing
not allowed
Shock check not in operation
according to EN 60068-2-27
Halve sine in 3 axis:
10g / 11ms
Fig. 5-1:
Conditions for transport
5.2
Storing the Devices
Conditions
temperature
-25 ... 55 °C
relative humidity
5 ... 95%;
climatic category 1K3
absolute humidity
1 ... 29 g/m
3
climatic category 1K3
moisture condensation
not allowed
icing
not allowed
Fig. 5-2:
Conditions for storage
In Case of Long Storage Periods
The power supply units contain sensitive electrolytic capacitors.
Therefore, in the case of long storage periods, operate the power supply
units once a year for at least 1 hour with power on (DC bus voltage must
be applied).
Summary of Contents for Rexroth IndraDrive HMV01.1E-W0030
Page 30: ...5 2 Transport and Storage Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 40: ...6 10 Mechanical Mounting Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 88: ...9 8 Control Mains Contactor Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 122: ...13 22 Appendix Rexroth IndraDrive DOK INDRV HMV PR01 EN P Fig 13 25 HFD01 2 480 0026 ...
Page 123: ...Rexroth IndraDrive Appendix 13 23 DOK INDRV HMV PR01 EN P Fig 13 26 HFD02 2 480 0026 ...
Page 130: ...14 6 Index Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 131: ......