Rexroth IndraDrive
Appendix
13-13
DOK-INDRV*-HMV-*******-PR01-EN-P
Fusing with Direct Mains Supply
Fusing the mains supply can implement, with power circuit breakers or
slow-blow fuses of the gL/gG type:
HMV01.1E-
Fusing
[A]
Power Circuit Breaker
Setting [A]
Wire cross
section
[mm²]
W0030
63
50
16
W0075
160
125
50
W0120
250
200
120
HMV01.1R-
Fusing
[A]
Power Circuit Breaker
Setting [A]
Wire cross
section
[mm²]
W0018
35
30
6
W0045
80
70
25
W0065
125
100
50
Fig. 13-13: Fusing with direct mains supply
13.4 Grounding the Power Supply System
HMV01.1E and HMV01.1R can be operated from three-phase systems
with grounded neutral points or phases without control-to-load isolation.
With ungrounded mains (IT mains) there is the increased danger that
unacceptably high overvoltages could occur between the phase and the
housing. Both the HMV01.1E and HMV01.1R can be protected against
unacceptable overvoltages,
•
if they are connected via an isolating transformer (the star point of
the output side and the PE connection of the power supply unit are
connected over one grounding rail)
- or -
•
if the unit is protected by over voltage suppressers.
Note:
Connecting the HMV01.1E and HMV01.1R via an isolating
transformer offers the best protection against overvoltage and
the greatest operating safety.
Grounded three-phase mains
Ungrounded three-phase mains
Summary of Contents for Rexroth IndraDrive HMV01.1E-W0030
Page 30: ...5 2 Transport and Storage Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 40: ...6 10 Mechanical Mounting Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 88: ...9 8 Control Mains Contactor Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 122: ...13 22 Appendix Rexroth IndraDrive DOK INDRV HMV PR01 EN P Fig 13 25 HFD01 2 480 0026 ...
Page 123: ...Rexroth IndraDrive Appendix 13 23 DOK INDRV HMV PR01 EN P Fig 13 26 HFD02 2 480 0026 ...
Page 130: ...14 6 Index Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 131: ......