5.3
Transporting the components
Ambient and operating conditions for transport
Description
Symbol
Unit
Value
Temperature range
T
a_tran
°C
-20 … +70
Relative humidity
%
5 … 95
Absolute humidity
g/m
3
1 … 60
Climatic category (IEC 721)
2K3
Moisture condensation
Not allowed
Icing
Not allowed
Tab. 5-3:
Ambient and operating conditions for transport
5.4
Storing the components
Risk of damage to components from long-
term storage!
NOTICE
Some components contain electrolytic capacitors which may deteriorate dur‐
ing storage.
When storing the following components for a longer period of time, run them
once a year for at least 1 hour:
●
Converters and supply units: Operated with mains voltage U
LN
●
Inverters and DC bus capacitor units: Operated with DC bus voltage
U
DC
Ambient and operating conditions for storage
Description
Symbol
Unit
Value
Temperature range
T
a_store
°C
-20 … +55
Relative humidity
%
5 … 95
Absolute humidity
g/m
3
1 … 29
Climatic category (IEC 721)
1K3
Moisture condensation
Not allowed
Icing
Not allowed
Tab. 5-4:
Ambient and operating conditions for storage
Bosch Rexroth AG
DOK-INDRV*-HCS01******-PR05-EN-P
120/341
Rexroth IndraDrive CsDrive Systems with HCS01
Condition as supplied, identification, transport and storage