6-18
Electrical Data
Rexroth IndraDrive C HCS03.1
DOK-INDRV*-HCS03.1****-PR02-EN-P
X3, Mains Connection
Operation in IT mains is possible without restrictions up to a pulse
frequency = 8 kHz. Operation at a pulse frequency of > 8 kHz is not
allowed.
For operation in grounded IT mains take into account that when filter HNK
is used, leakage currents can occur which might trigger circuit breakers or
earth-leakage monitors.
Install an isolating transformer.
HCS03.1E-
Type
No. of
poles
Type of design
W0070
Connector
4
Screw connection
W0100
Terminal block
3
Screw connection for M6 ring
cable lugs
W0150
Terminal block
3
Screw connection for M6 ring
cable lugs
W0210
Terminal block
3
Screw connection for M10 ring
cable lug
Fig. 6-22:
Design mains connection
Identification of the individual connections:
Identification
Significance
L1
phase 1
L2
phase 2
L3
phase 3
(PE)
equipment grounding conductor
Fig. 6-23:
Identification of the individual connections mains connection
HCS03.1E-
Cross section
[mm²]
Cross section
flexible
[mm²]
Cross section
AWG
W0070
16
-
6
W0100
35
-
2
W0150
50
2*25
0
W0210
95
2*50
4/0
Fig. 6-24: Connection cross sections mains connection
HCS03.1E-
Tightening torque [Nm]
W0070
1.5
W0100
6
W0150
6
W0210
25
Fig. 6-25:
Tightening torques mains connection
Remedy
Design
Connection Cross Section
Tightening Torque
Summary of Contents for Rexroth IndraDrive C HCS03.1
Page 6: ...IV Contents Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 12: ...1 6 Indroduction Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 30: ...4 4 Identification Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 38: ...5 8 Mechanical Data Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 72: ...8 6 Replacing Devices Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 84: ...11 4 Index Rexroth IndraDrive C HCS03 1 DOK INDRV HCS03 1 PR02 EN P ...
Page 85: ......