28 / 36
IndraControl XFE 01.1
Error messages of the status LEDs
Bosch Rexroth AG
R911345570, Edition 06
LED
LED display Cause
BF
Red
•
Master:
LED flashes (2 Hz): Configuration error: Not all configured I/O
devices are connected
LED on (together with SF “red on"): Hardware problem, field
bus stack cannot be loaded or there is no valid master license.
LED on (together with SF “red on"): No link, double IP, Hidden
Loop
•
Slave:
LED flashes (2 Hz): No data exchange
LED on: No configuration or slow physical connection, no phys-
ical connection or double IP
During normal mode (without errors), the LEDs “SF” and “BF” can also be on, but at low
intensity. This does not signal an error state. Check, whether additional diagnostic information
in available in the diagnostic log.
Table 19: Profibus
LED
LED display Cause
Stat
LED is acycli-
cally on
Module not configured
BF
LED is perma-
nently on
No connection
LED flashes Slave diagnostics
Table 20: Sercos
LED
LED display Cause
S
LED is off
No data is sent
L
LED is off
No connection present
Table 21: CAN
LED
LED display Cause
PW
LED is off
Voltage error of the CAN voltage
ERR
LED is red
Bus error, refer to the CANopen standard “CIA 303 Part 3: Indicator
Specification”
RUN
LED is off
Communication error, refer to the CANopen standard “CIA 303 Part
3: Indicator Specification”
13.1.1 Error cases after commissioning the CAN module
The following errors can be displayed when commissioning the CAN module, also refer to
Chapter 11.1 “Commissioning notes ” on page 24
: