11 DVD drive
12 Five PCI and one PCIe slot for exten‐
sion cards
13 Mounting bolt
14 Depending on the device variant Ma‐
chine function keys (M-keys) R1 to R8
(assignment see project planning
manual)
15 Fan
Fig.12-1: Illustration of a VSP panel PC with maximum equipment
12.2
Operating and Error Display
There are four LEDs as on the top of the front panel to display the device conditions
and errors of the connected control cabinet PC. Take one of the following measures if
one of the succeeding LEDs displays an error or a note.
LED
Display
Meaning
Measure
Vin
LED green
Normal mode
-
LED off
No supply voltage DC 24 V
Check supply voltage
HDD
LED yellow
Hard disk access
-
LED flashes
yellow
Warning: SMART analysis
identifies errors
Exchange hard disk
TEMP
LED off
Normal mode
-
LED flashes
red
Fan does not rotate or rotates
too slowly
Check fan in device!
LED red
Overtemperature
Reduce surrounding air tem‐
perature!
UPS
LED off
Normal mode
-
LED red
The panel PC is currently run‐
ning in the UPS operating
mode. I.e. no supply voltage is
provided at the UPS!
Restore power supply and ini‐
tiate controlled restart of the
panel PC!
Fig.12-1: LEDs for operating and error display on the connector panel
If the panel PC is shut down under Windows and the 24 V input voltage is
switched off, the input voltage can only be switched on again when the
Vin-LED is off.
Bosch Rexroth AG
Device Description
DOK-SUPPL*-VSP*XX.3***-IT01-EN-P
Rexroth IndraControl VSP xx.3 Panel PC
30/43