Name at the
housing
Connection type
Connector type (integra-
ted)
Mating connector or cable
(from outside)
XCDI+tx2
CDI+ interface to the sec-
ond operator display
RJ45 socket
RJ45 plug
Functional earth (FE)
M5
Ring cable lug
Tab. 9-1: Interfaces and connections at the CDI+ splitter
9.1 24 V voltage supply and digital 24 V inputs
9.1.1 VAC 08.1 – Connection terminal X1S1
Pin
Labeling
Function
1
24 +
24 V supply voltage
2
24 –
0 V supply voltage
3
MOD/SEL –
0 V for switching and MOD
4
SEL +
24 V switching input
5
MOD +
Enables the operation at both oper-
ator displays or at no operator dis-
play
Tab. 9-2: Pin assignment X1S1
For the function on the digital inputs, refer to:
tion of the digital inputs" on page 24
.
Operating the operator display as well as the USB data traffic only
possible at the active operator display. The screen is always output
on both operator displays