Error code
Error cause
Description
Solution
Dec
Hex
6155
0x180B
TUNID mismatch
The values of SNN and SDID en‐
tered at the DIP switch do not
match the values entered under
"Safe Configuration".
Compare the DIP switch position
with the values entered under
"Safe Configuration". Note that
0x600000000 is added to the SNN
value.
6156
0x180C
Data age of valid mes‐
sage greater than NTE
The exchanged data is older than
NTE
Increase the NTE value under
"Safe configuration".
6157
0x180D
Time coord. message
not received in allowed
time
The "time coordination message"
was not received in the expected
time
Increase the NTE value under
"Safe configuration".
6158
0x180E
Connection in use or
Duplicate For‐
ward_Open
It is either tried to reconfigure an
existing connection or a "forward
open" was sent twice.
The configuration of the new con‐
nection is incomplete: Ensure that
the SCCRC is provided with the
same value in "Safe Configura‐
tion" and in "Safe Parameteriza‐
tion". Check whether the "Safety
application" was compiled without
errors. Log in to the standard ap‐
plication to automatically apply the
required changes. "Duplicate For‐
ward open": Increase the NTE val‐
ue under "Safe configuration".
6160
0x1810
SafetyClose refer‐
enced an unknown
connection
The module received a Safety‐
Close with incorrect connection
parameters
Compare the DIP switch position
with the values entered under
"Safe Configuration". Note that
0x600000000 is added to the SNN
value.
Change SNN or SDID using DIP
switches. The saved connection
parameters are deleted upon a
new voltage startup.
6161
0x1811
Initialization not com‐
pleted within time limit
Connection could not be establish‐
ed.
Start the Safety application again.
6304
0x18A0
Operator made invalid
settings on DIP switch.
DIP switch position invalid. The
DIP switch position may not be 0
for SNN and SDID.
Set a value other than 0 for SNN
and SDID. Change SNN or SDID
using DIP switches. The DIP
switch values are applied after a
new voltage startup.
Tab. 13-3:
Parameter errors: CSos parameters
Bosch Rexroth AG
DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
68/85
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
CSos parameters and device parameters