Wire the connectors as required according to the application.
Proceed as follows to wire the connectors:
●
Strip the line to a length of 8 mm. Wiring is provided without core end
sleeves. However, core end sleeves may be used, if desired. In this case,
do ensure that the core end sleeves are properly crimped.
●
Put a screwdriver into the actuation slot of the corresponding terminal point
(figure
, A) so that the core can be inserted into the opening of the
spring. Insert the core (figure
, B). Pull the screwdriver out of the
opening. This fixes the core. We recommend you to label the cores and
the terminal points after the installation.
For further information on the connection method, please refer to
the \2\ Rexroth Inline PROFIBUS DP; Application Manual (see
chapter 1.3 "Further Documentation" on page 6
Connecting Shielded Cables Using the Shield Connector
Fig.8-13:
Connecting the shield to the shield connector
The connection of a shielded cable is described by example of an "analog ca‐
ble".
For connection, proceed as follows:
Stripping the Lines
●
Strip the outer sheath of the line to the desired length (a) ①.
DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
Bosch Rexroth AG
63/81
Installation and Maintenance