The maximum current carrying capacity of the Inline voltage is 0.8 A. Thus, the
total current consumption of all Inline modules must not exceed this maximum
value of 0.8 A.
If the total power consumption of all the Inline modules exceeds this value of
0.8 A, the 7.5 V Inline supply voltage can be fed using the terminal R-IB IL 24
PWR IN/R-PAC. This terminal feeds additional 2 A.
+24 V Analog Supply (UANA)
The +24 V analog voltage is generated from the voltage U
LS
. It starts in the
IndraControl L10 and is supplied through all Rexroth Inline I/O modules by the
lateral contacts (voltage jumper).
The output signals of the analog modules are generated from the analog circuit
in the analog terminals.
The voltage in this circuit is 24 V.
The analog voltage U
ANA
is generated from the IndraControl L10 from the supply
voltage U
LS
.
The maximum current carrying capacity of U
ANA
is 0.5 A.
PWR IN
Voltage module at the IndraControl
R-IL 24 PWR
IN
Power terminal
R-IL 24 SEG/
F
Segment terminal with fuse
Fig.7-11:
Inline supply with analog circuit
Remarks for wiring, please refer to
chapter 8.2 "Electric Installation" on page
7.3
Digital Inputs and Outputs
7.3.1
Address Assignment of Inputs and Outputs
The 8 digital inputs and 4 digital outputs available on the slots 1 to 3 of the
IndraControl L10 (from left to right) are assigned to light-emitting diodes and bit
addresses according to the following table:
8 digital inputs
4 digital outputs
Slot
1
2
3
Status LED
1
2
3
4
1
2
3
4
1
2
3
4
28/54
Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraControl L10 | Project Planning Manual
Connections and Interfaces
Current Carrying Capacity
Function
Voltage
Generation
Current Carrying Capacity