Data
Choke HLL05.1x
-04M0-…
Inductance
[mH]
Continuous
current
[A]
Power dissipation
[W]
Allowed
leakage ca‐
pacitance
[µF]
Degree of
protection
Ambient tem‐
perature
1)
[°C]
Weight
[kg]
Air
Water
2)
S0202 (air-cooled)
4
202
380
-
1.2
IP00
40
27
S0202 (water-cooled)
4
202
230
400
1.2
IP00
40
23
S0243
4
243
240
430
1.2
IP00
40
25
S0303 (air-cooled)
4
303
400
-
1.2
IP00
40
38
S0303 (water-cooled)
4
303
270
480
1.2
IP00
40
33
S0380
4
380
330
580
1.2
IP00
40
36
S0475
4
475
420
760
1.2
IP00
40
86
S0603
4
603
530
940
1.2
IP00
40
98
S0720
4
720
540
960
1.2
IP00
40
110
S0942
4
942
680
1220
1.2
IP00
40
152
1)
Maximum ambient temperature: 55 °C (with derating)
2)
Maximum water inlet temperature: 60 °C
Tab. 8-51:
HLL05.1F, data
Temperature monitoring contact
●
Trigger temperatureAuslösetemperatur: 160 °C
●
N/C in one of the windings
●
Electric switching capacity:
–
1 A
–
AC 250 V
–
DC 24 V
DOK-INDRV*-HXX05******-PR02-EN-P
Bosch Rexroth AG
243/407
Rexroth IndraDrive ML Drive Systems with HMU05
Cables, accessories, additional components