![Bosch Rexroth HMU05.1N Series Project Planning Manual Download Page 184](http://html.mh-extra.com/html/bosch/rexroth-hmu05-1n-series/rexroth-hmu05-1n-series_project-planning-manual_44851184.webp)
XG34, mains contactor (contact)
View
Connec‐
tion
Function
1
Connection to outer conductor L
2
Mains contactor connection
Tab. 8-28:
Function, pin assignment, properties
Mechanical data
Screw connection at connector
Unit
Min.
Max.
Tightening torque
Nm
0.6
0.8
Connection cable
Stranded wire without ferrule
mm
2
0.2
2.5
AWG
24
12
Connection cable
Stranded wire with ferrule
mm
2
0.25
2.5
Stripped length
mm
10
Tab. 8-29:
Mechanical data
Electrical data
Unit
Min.
Max.
Switching voltage
V
5Vac / 5Vdc
~250Vac / 50Vdc
Continuous current
A
1
Switching current
A
5
Load current
mA
10
Switching cycles
3 × 10
5
Tab. 8-30:
Electrical data