Identifica‐
tion
Function
PE
Connection to equipment grounding system
Connecting bolt
Unit
Min.
Max.
Hole diameter
mm
13
Tightening torque M10
Nm
25
Tightening torque M12
Nm
48
Occurring current load and minimum required
connection cross section
See technical data of device used (I
LN
and A
LN
)
Occurring voltage load
See technical data of device used (U
LN
or U
LN_nenn
)
Tab. 6-1:
Function, pin assignment, properties
Minimum cross section of equipment grounding connection
Outer conductor cross section
Min. cross section of equipment ground‐
ing conductor
Leakage current ≥ 3.5 mA
16 mm
2
(6 AWG)
16 mm
2
(6 AWG)
25 mm
2
(4 AWG)
35 mm
2
(2 AWG)
50 mm
2
(1/0 AWG)
25 mm
2
(4 AWG)
70 mm
2
(2/0 AWG)
35 mm
2
(2 AWG)
X mm
2
(X × 0.5) mm
2
(valid for X ≥ 50)
Tab. 6-2:
Minimum cross section of equipment grounding connection
L1, L2, L3, mains/motor connection
Important notes
Lethal electric shock by live parts with more
than 50 V!
WARNING
Exclusively operate the device
●
with plugged on connectors (even if there haven't been any lines con‐
nected to the connectors) and
●
with connected equipment grounding conductor!
Notes on installation
●
The cable is connected to the connection point using ring cable lugs.
●
Measure the necessary cross section of the connection cables accord‐
ing to the determined phase current I
LN
and the mains fuse.
Bosch Rexroth AG
DOK-INDRV*-HXX05******-PR02-EN-P
126/407
Rexroth IndraDrive ML Drive Systems with HMU05
Mounting and installation