Rexroth Diax 04 HVE/HVR
Instructions for Use
5-9
DOK-DIAX04-HVE+HVR*UL*-IB01-EN-P
1
2
3
4
5
6
max. 100 mA
max. 2 A
+15 VM
-15 VM
0 VM
+24 VL
0 VL
n/c
7
X4
R02hva1B.fh7
shield
1)
X2
X3
X4
X6
X7
X0
1)
only for HVE
Fig. 5-21:
Terminal assignment X4
Control voltages 24 VL and
±
15 VM can be tapped off of terminal strips
X4/1…X4/6. These terminals are intended for measuring and test
purposes.
If these voltages are used outside of the drive system, then make sure
that no interference voltages are coupled in (short, shielded lines). The
load carrying ability of the control voltages is correspondingly reduced by
the drive controllers.
The control voltage outputs are short-circuit proof. The maximum
permissible load must not be exceeded in order not to endanger the
functions of the drives.
X5, Mains connection
DANGER
Lethal electric shock caused by live parts with
more than 50 V!
⇒
Connect the protective conductor connections to the
protective conductor system of the control cabinet.
⇒
Check the continuity of the protective conductors
from the mains connection to the connected motors.
hvx_X5.fh7
U
V
W
X5
Fig. 5-22:
Terminal X5 with HVx02.2 and HVx03.2
Terminal assignment
Terminal X5