Menu overview
Rego 1000 – 6 721 831 662 (2021/03) en
7
5
Menu overview
The top menu for the customer is:
•
1 Room temperature
•
2 Hot water
•
3 Holiday
•
6 Energy measurements
•
7 Timers
•
8 External control
•
12 General
•
13 Alarms
•
14 Access level
•
15 Return to factory settings
Factory value = F-value
HP x = Heat pump 1 or 2 / Compressor 1 or 2
No.
Name
F value
Min.
Max.
Alternative
1
Room temperature
1.1
Circuit 1 Heating
1.1.5
Heat curve
1.1.6
Compressor 1 operating time on/off
20,0
10,0 ( Comfort )
30,0 ( Economy )
1.1.7
Compressor 2 operating time on/off
20,0
10,0 ( Comfort )
30,0 ( Economy )
1.1.10
Room sensor
1.1.10.1
Room temperature influence (with room sensor)
3,0
0,0
10,0
1.1.11
Room temperature program
1.1.11.1
Active program
HP optimized
HP optimized /
Program 1 / Program 2
1.1.11.2
View/edit active program
1.1.11.3
Room temperature normal
20,0 °C
10,0 °C
35,0 °C
1.1.11.4
Temperature increase/decrease (no room sensor)
=
--/-/+/++
1.1.11.6
Room temperature influence
3,0
0,0
10,0
1.1.11.7
Room temperature exception
17 °C
10 °C
30 °C
1.1.11.8
Copy to all heating circuits
No
No / Yes
1.3
Circuit 2 (option)
1.3.5
Heat curve (see 1.1.5)
1.3.7
Room sensor (see 1.1.10)
1.3.8
Room temperature program (see 1.1.11)
1.4
Circuit 3 (option) (see 1.3)
1.5
Circuit 4 (option) (see 1.3)
1.10
General
1.10.1
Summer/winter operation
1.10.1.1
Winter operation
Automatic
On / Automatic / Off
1.10.1.2
Outdoor temperature limit for change over
18 °C
5 °C
35 °C
2
Hot water
2.2
Hot water mode
Economy
Comfort / Economy
2.3
Extra hot water
2.3.1
Extra hot water duration
0h
0h
48h
2.3.2
Extra hot water stop temperature
65,0 °C
50,0 °C
65,0 °C
2.4
Hot water peak
2.4.1
Day of the week
None
None /Day/ All
2.4.2
Interval in weeks
1
1
4
2.4.3
Start time
3:00
0:00
23:00
2.5
Hot water program
2.5.1
Active program
Always hot water
Always hot water /
Program 1 / Program 2
2.5.2
View/edit active program
3
Holiday
3.1
Circuit 1 and hot water
3.1.1
Activate holiday function
No
No / Yes
3.1.2
Start date
3.1.3
Stop date
3.1.4
Room temperature
17,0 °C
10,0 °C
35,0 °C
3.1.5
Copy to all heating circuits
No
No / Yes
3.1.6
Block hot water production
No
No / Yes
3.2
Circuit 2 (option) (see 3.1)
3.3
Circuit 3 (option) (see 3.1)
3.4
Circuit 4 (option) (see 3.1)
6
Energy measurements
Table 3 Menu overview