Event:
Short circuit fault: output A and/or B
Group
: Fault
Occurrence:
Short circuit fault: output A and/or B.
Originator
: Amplifier.
Recommended action
: Check/replace loudspeakers, lines and connections.
Event:
Amplifier channel fault: spare
Group
: Fault
Occurrence:
Logs the failure of the Amplifier spare channel.
Originator
: Amplifier.
Recommended action
: Check/replace amplifier input, output and power signals.
Event:
End of line fault: output A and/or B
Group
: Fault
Occurrence:
End of line fault: output A/B.
Originator
: Amplifier channel.
Recommended action
: Check/replace EOL board, lines and connections.
18.2.3
Multifunction power supply (MPS)
The following
fault
events can
only
occur on multifunction power supply devices.
Event:
Amplifier 1/2/3 lifeline supply fault
Group
: Fault
Occurrence:
Logs the failure of the 18 V power supply for amplifier 1 and/or 2 and/or 3.
Originator
: MPS
Resolve:
When the error is no longer present or when the device disconnects.
Recommended action
:
–
Check the MPS lifeline 18 V output power supply, lines and connections.
–
Check the amplifier 18 V output power supply input, lines and connections.
Event:
Amplifier 1/2/3 lifeline audio fault
Group
: Fault
Occurrence:
Logs the failure of the lifeline audio output for amplifier 1 and/or 2 and/or 3.
Originator
: MPS
Resolve:
When the error is no longer present or when the device disconnects.
Recommended action
:
–
Check the MPS lifeline, audio lines and connections.
–
Check the amplifier lifeline, audio lines and connections.
Event:
Battery supply fault: outpu 1/2/3
Group
: Fault
Occurrence:
Logs the failure of the battery power supply for amplifier 1 and/or 2 and/or 3.
Originator
: MPS
Resolve:
When the error is no longer present or when the device disconnects.