![Bosch PM1-LISD Installation And Operation Manual Download Page 45](http://html.mh-extra.com/html/bosch/pm1-lisd/pm1-lisd_installation-and-operation-manual_50609045.webp)
Operation
The Loudspeakers Line Isolator System is autonomous. Colored LEDs on the front panel of the
Master Unit indicate the status of the system.
Master Unit (front panel)
1 2 3 4 5 6
7
5
3
1
2
4 6 8
No. LED
Color
Description
1
Mains power
Green
ON
–
Master Unit is supplied with mains power
and is switched on.
OFF –
Master Unit is not supplied with mains
power or is switched off.
2
Mains fault
Yellow
ON
–
Master Unit is not supplied with mains
power but is supplied with backup power,
and mains supervision is enabled.
OFF –
Master Unit is supplied with mains power.
–
Master Unit is switched off or not supplied
with mains or backup power.
–
Mains supervision is switched off.
3
Backup power
Green
ON
–
Master Unit is supplied with backup power.
OFF –
Master Unit is not supplied with backup
power.
–
Backup power voltage is below 18 volts.
4
Backup fault
Yellow
ON
–
Backup power voltage is below 21 ±1 volts
and the Master Unit is supplied with mains
power and battery power supervision is
enabled.
OFF –
Backup power is present.
–
The Master Unit has no mains power and
backup power is below 18 volts.
–
The battery supervision is set to OFF.
8
8.1
Loudspeakers Line Isolator System
Operation | en
45
Bosch Security Systems B.V.
Installation and Operation Manual
2014.03 | V1.1 |