wLSN
wLSN Devices | en
53
Bosch Security Systems, Inc.
System Reference Guide
F01U138553 | 01 | 2010.05
5.13.3
Testing
Test the detector at least once each year. Test the detector
with the 13-332 Sound Sensor Tester.
Figure 5.21
13-332 Sound Sensor Tester
Entering Test Mode
Place the detector in Test Mode. In Test Mode, the detector’s
LED ENABLE switch (
Item 8
) is overridden.
You can enter the Test Mode locally or remotely.
To enter the Test Mode locally:
1.
Carefully open the service door of the detector.
2.
Insert a screwdriver into the slot next to the sensitivity
switches (
Item 1
,
).
3.
Touch both test pads at the same time with the tip of the
screwdriver.
The EVENT LED (green) (
Item 6
,
flashes once each second. If the green LED does not flash,
repeat
Steps 2
and
3
.
Callout
Description
1
ACTIVATE/TEST switch
2
Start button
3
FLEX/MAN switch
1
ACTIVATE
TEST
FLEX
MAN
2
3
AC
TIV
AT
E
TE
ST
FL
EX
MA
N
13-332
WARNING!
The 13-332 Sound Sensor Tester produces extremely loud
sounds and can be hazardous to hearing when used at close
range. Do not point the 13-332 toward someone’s head.