Modular fire panel
Installation | en
107
Bosch Sicherheitssysteme GmbH
System Information
07.2020 | 12.0 | F.01U.028.089
!
Caution!
Electromagnetic compatibility
Only use 4-wire cabling when connecting the peripherals.
–
EOL modules can be used with CZM 0004 A from software version 1.1.10 onwards.
–
All additional voltage outputs (AUX 1-AUX 4) can be switched on and off simultaneously.
–
Two and four-wire conventional components can be connected.
–
Note the maximum line resistance:
–
25 Ohm for conventional lines with FMC-300RW or automatic fire detectors
–
12 Ohm for conventional lines with FMC-120-DKM manual call points
The technical data can be found in
CZM 0004 A 4 Zone Conventional Module, page 151.
4.9.5
ENO 0000 B Fire Service Interface Module
The ENO 0000 B is used to connect fire service equipment:
–
Transmission device to the fire brigade
–
Key deposit
–
Signal lamp (e.g. BEGA flush-mounting lamp or BL 200)
–
FSE release element monitoring
–
Four freely programmable changeover relays
Notice!
The requirements of the local fire department must be taken into account during
programming.
The module is used almost exclusively in Germany.
Figure 4.56:
ENO 0000 B Fire Service Interface Module
Labeling
Connection
A
Ground
B
Transmission unit control
C
Feedback contact
ÜE
Automatic dialer and transmission unit fault
NQuit
Acknowledge
GND
Ground
ÜE+ | ÜE-
Power supply of transmission unit
1
Monitoring key deposit