Bosch FMC-210-SM Installation Manual Download Page 1

Fire Alarm Systems | FMC‑210‑SM Single Action Call Points

The FMC‑210‑SM Single Action Call Points are used for
manual triggering, and can be used in the Local
SecurityNetwork LSN and LSN improved. The
FMC‑210‑SM Single Action Call Points are designed for
indoor deployment.

Functions

1

1

2

2

3

3

4

5

With single action call points, the alarm is triggered when
the glass plate (2) is broken and the button (3) springs
up.
This activates the microswitch for alarm triggering and the
indicator LED (4) blinks.
The call point (3) can be reset after inserting a new glass
pane (2) and closing the door of the single action call
point (1). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.

Individual call point identification with display of the call
point address on the fire panel ensures the quick location
of the triggered call point.

Certifications and Approvals

FMC‑210‑SM‑G‑R applies to

EN 54‑11:2001/A1:2005

EN 54‑17:2005

Region

Certification

Germany

VdS

G 207008   FMC-210-SM-G-R

Europe

CPD

0786-CPD-20316   FMC-210-SM-G-R

Installation/Configuration Notes

Manual call points must be mounted visibly along

escape and rescue routes (e. g. exits, passageways,

stairwells) and be easily accessible.

An installation height of 1400 mm ±200 mm, measured

from the middle of the manual call point to the floor,

must be maintained.

Manual call points must be adequately illuminated by

sunlight or another light source (including emergency

lighting if present).

FMC‑210‑SM Single Action Call Points

Alarm triggering by breaking of the glass pane

Automatic or manual detector addressing via rotary

switch possible

Indicator LED for alarm or for inspection evaluation

Call point query routines with evaluation and multiple

transmission

Individual call point identification

Maintains LSN loop functions in the event of wire

interruption or short-circuit thanks to two integrated

isolators

www.boschsecurity.com

Summary of Contents for FMC-210-SM

Page 1: ...tifications and Approvals FMC 210 SM G R applies to EN 54 11 2001 A1 2005 EN 54 17 2005 Region Certification Germany VdS G 207008 FMC 210 SM G R Europe CPD 0786 CPD 20316 FMC 210 SM G R Installation Configuration Notes Manual call points must be mounted visibly along escape and rescue routes e g exits passageways stairwells and be easily accessible An installation height of 1400 mm 200 mm measured...

Page 2: ...led at a distance of max 40 m VDE 0833 Part 2 Point 7 2 6 Installation The cable duct can be surface mounted or flush mounted Installation in fire hose cabinets is possible in three ways 135 mm 140 mm 2 5 mm 2 mm 139 mm 1 2 3 149 5 mm 12 5 mm Pos Description 1 Installation depth version 1 ca 40 mm 2 Installation depth version 2 14 mm 3 Installation depth version 3 min 30 mm Parts Included TypeNumb...

Page 3: ...g type A for LSN improved FMC 210 SM G R Accessories FMX FSO LSN Punched Self adhesive Foil Sets Blank For the labeling field of manual call points of the Series FMC 210 1 unit 10 sheets FMX FSO LSN FMC FST DE Printed Labeling Foils for the Upper Label Field For yellow and blue manual call points of Ser ies FMC 120 and FMC 210 1 unit 5 sheets FMC FST DE FMC SPGL DEIL Spare Glasses For manual call ...

Page 4: ...y Systems B V P O Box 80002 5600 JB Eindhoven The Netherlands Phone 31 40 2577 284 Fax 31 40 2577 330 emea securitysystems bosch com www boschsecurity com Asia Pacific Robert Bosch SEA Pte Ltd Security Systems 11 Bishan Street 21 Singapore 573943 Phone 65 6258 5511 Fax 65 6571 2698 apr securitysystems bosch com www boschsecurity asia Represented by Bosch Security Systems 2011 Data subject to chang...

Reviews: