Alarm Cable Requirements
The terminal connector contains three Alarm In connections, two Alarm Out connections, and
1 relay.
Max. wire diameter
AWG 22-28 for both stranded and solid
Alarm output relay
switching capability
Max voltage 30 VAC. Max 0.5 A continuous, 10 VA.
Alarm Inputs
Three (3) non-supervised Programmable for “normally open” or
"normally closed”
Alarm Outputs
Two (2) open collector/transistor outputs 32 VDC @ 150 ma
max.
1 dry contact relay
Audio Cable Requirements
Wire Type
Shielded Coax (recommended)
Distance
Typically 10 m (33 ft), but depends on the signal level
Gage
Typically 22 AWG, but depends on the style of connector used
Shield
Bare copper braid: 95% coverage
Center conductor
Stranded bare copper
Making the Connections
All required connections are accessible by removing the rear end cap.
Notice!
Take care not to drop the end caps to prevent damage to the cap threads.
Notice!
Ensure to disconnect all cables from the interface board before removing the inner mounting
bracket assembly from the housing.
Refer to the following figure when making connections:
Figure 6.1: User Connections on User Interface Board