Displays on the Module
8–1
1070 066 028-101 (01.05) GB
8
Displays on the Module
8.1
Status / warning displays
LED
Status
Measures
FG
Axis enable external if
D
24 V at X06.3/4 (FG) present
–
FGI
Enable internal if
D
24 V at X06.3 (FG) present
D
Central enable by VM present
D
no faults
–
3-digit 7-segment display
Computer
booted
TEMP
STA
Operating display:
D
STA is present if:
–
computer has been booted
– no
faults
Temperature status:
D
TEMP is present if:
Temperature of the heat sink or the mo-
tor (with active bimetal function) is within
the permitted range
D
TEMP relay is closed
–
If no display (temp. exceeded):
D
Check air supply, fan
D
Reduce clock frequency or load
D
Select motor with higher rating
D
Verify bimetal setting
More operating data can be read from the 7-segment display. For operation,
refer to section 3.3.
Read
from
DSS
Unit
Description
A00
A-0-1000
Hz
Actual output frequency f
act
Current motor frequency
A01
A-0-1001
Hz
Setpoint output frequency
f
set
Specified output frequency
A02
A-0-1002
A
Total current
rms value of the total current
A03
A-0-1003
A
Active current
rms value of the active current
A04
A-0-1004
A
Reactive current
rms value of the reactive current
A05
A-0-1005
V
Motor voltage
rms value of the current motor voltage
A06
A-0-1006
V
Link voltage
Current value of the link voltage.
(Display = 350 V for voltage values
x
350 V)
A07
A-0-1007
kVA
Total power
Current total power
A08
A-0-1008
kW
Shaft output
Current mechanical shaft output of the motor