Commissioning
5–21
1070 066 028-101 (01.05) GB
5.1.15
Analog outputs
Analog outputs X23.8 and X23.9 can be assigned the current operating data.
.
For proper output signals, the rated motor power (P05) must be input.
Level: 0 ... +10 V,
Current and power signals can be adjusted within the following ranges (P41,
P42):
Assignment
10 V
¢
...
[ ] = factory setting
DM..4K
DM..8K
DM..15K
DS..15K
DM..30K
DM..30A
DM..45K
DM..45A
DS..45K
DM..85B
DM..140D
Actual output frequency (AA0) [Hz]
max. output frequency (P02)
Total current, rms (AA1)
[A]
Standardization via P41:
Active current, rms (AA2)
[A]
Reactive current, rms (AA3)
[A]
0.9...15
[9.5]
1.5...25
[15.9]
3.1...50
[31.8]
4.7...75
[47.7]
9.5...150
[95.4]
12.7...200
[127]
Motor voltage (AA4)
[V]
Link voltage (AA5)
[V]
1000 V
Standardization via P42:
Total power (AA6)
[kVA]
Shaft output (AA7)
[kW]
0.4...7.5
[7.5]
0.7...12.5
[12.5]
1.5...25
[25]
2.3...37.5
[37.5]
4.6...75
[75]
6.2...100
[100]
Utilization (AA8)
[%]
200 %
Heat sink temperature (AA9)
[
_
C]
100
_
C
P39 (A-0-0039)
Assignment of analog output X6.8
factory
setting
all
DMs, DS
AA0
(0)
AA1
(1)
AA2
(2)
AA3
(3)
AA4
(4)
AA5
(5)
AA6
(6)
AA7
(7)
AA8
(8)
AA9
(9)
P40 (A-0-0040)
Assignment of analog output X6.7
factory
setting
all
DMs, DS
AA0
(0)
AA1
(1)
AA2
(2)
AA3
(3)
AA4
(4)
AA5
(5)
AA6
(6)
AA7
(7)
AA8
(8)
AA9
(9)