Commissioning
5–10
1070 066 028-101 (01.05) GB
5.1.6
Setpoint adjustment
P13 (A-0-0013)
Setpoint source
The frequency setpoint can be input using an external analog voltage or cur-
rent signal or internally. The specified direction of rotation applies to properly
connected motors when looking towards the shaft end.
If an external voltage signal is used, 7 different setpoint smoothing options
(t
sm
) may be selected.
.
Before selecting one of the following possibilities, the external enable
signal FG must be deactivated.
factory
setting
all
DMs, DS
EF1
(1)
EF2
(2)
EF3
(3)
analog
t
sm
=3.5 ms
P14 ccw
rotation
P14
cw rotation
EF4
(4)
EF5
(5)
EF6
(6)
EF7
(7)
EF8
(8)
EF9
(9)
analog
t
sm
=6.5 ms
analog
t
sm
=12.5 ms
analog
t
sm
=25 ms
analog
t
sm
=50 ms
analog
t
sm
=100 ms
analog
t
sm
=200 ms
analog:
$
5...13 VDC at X23.5/6 or
0...20 mA at X23.5/7 (X23.5/6 bridged)
P14 (A-0-0014)
Keyboard setpoint
The internal frequency setpoint is set with the or keys.
0.0
999 Hz
smallest step
Range [Hz]
factory
setting
all
DMs, DS
0.1
1
100
min.
max.
.
When P13 is changed over to ’EF1’ the keyboard setpoint is
automatically reset to ’0’.